Model | MPS0030 | MPS0050 | MPS0100 | MPS0150 | MPS0250 | MPS0500 |
AC(grid-connected) | ||||||
Rated power | 30kW | 50kw | 100kw | 150kw | 250kw | 500kW |
Rated current | 43A | 72A | 144A | 217A | 361A | 722A |
Voltage range | 320V-460V | |||||
Rated frequency | 50/60Hz | |||||
Frequency range | 45-55/55-65Hz | |||||
THDI | <3% | |||||
PF | 0.8lagging-0.8leading | |||||
AC connection | 3W+N+PE | |||||
Transformer | Yes | |||||
AC(off-grid) | ||||||
Apparent power | 33KVA | 55KVA | 110KVA | 165KVA | 275KVA | 550KVA |
Rated power | 50KW | 50KW | 100KW | 150KW | 250KW | 500KW |
Rated Voltage | 400V | |||||
Rated Current | 43A | 72A | 144A | 217A | 361A | 722A |
THDU | 鈮 | |||||
Rated frequency | 50/60Hz | |||||
Overload capability | 110%-10min120%-1min | |||||
PV | ||||||
Max. PV open-circuit | 1000VDC | |||||
voltage | ||||||
Max Power | 60/120KW | 120/180/240KW | 300/360KW | 600/660/720KW | ||
PV MPPT Voltage Range | 220-850V | |||||
MPPT Number | 1月2日 | 2002/3/4 | 5月6日 | 2010/11/12 | ||
Battery | ||||||
Battery Voltage | 150V-850V | 420V-850V | 500V-850V | |||
Battery Full Loading Operation Volaage Range | 150V-850V | 420V-850V | 500V-850V | |||
General data | ||||||
Dimension(WXDXH) | 800X800X1900mm | 1200X800X2050mm | 1800X800X2050mm | 2800X800X2050mm | ||
Weight | 440kg | 620kg | 900kg | 1250kg | 1700kg | 3520kg |
Environmental temperature | -25潞C~+55潞C | |||||
Relative humidity | 0-95%non-condensing | |||||
Protection degree | IP20 | |||||
Noise emission | 75dB(A)@1m | |||||
Max.imum altitude | 5000m(derate over 3000m) | |||||
Cooling | Forced-air | |||||
Communication | ||||||
Display | Touch screen LCD | |||||
Communication interface | RS485/CAN |
products DESCRIPTIONPRODUCTS
Energy Storage Hybrid Inverter (High Battery Voltage)
1.Flexible
* Various working mode can be flexibly.
* Flexible Battery Type(li-ion,lead-acid).
* PV controller can be expended to fexilitate flexible
2.Convinent
* Integreted design to support loads, batteries,power grids,diesel generators and PV be connected.
* Integrated EMS function, power supply security and stability,maximum utilization of new energy
3.Reliable
* Prediction intelligent battery management and discharge time.
* CAN and RS485 communication interface, modbus protocol.
* Seamless transfer between on and off grid.
*Strong load adaptability
*Perfect protection function to protect inverters and batteries